Stainless Steel Fire Damper Technical Specifications

August 18, 2025
Latest company news about Stainless Steel Fire Damper Technical Specifications

Functional Definition
Stainless steel fire dampers are critical safety devices in building ventilation and fire protection systems. Constructed from 304/316 stainless steel, they automatically isolate ductwork upon temperature activation to prevent fire spread.

I. Core Features

  1. Fire Protection Mechanism

    • Temperature Response‌:
      • Activation at 70°C (Fire Dampers) or 280°C (Smoke Exhaust Dampers)
      • Dual-trigger system: Gravity spring + shape-memory alloy thermal sensor
    • Sealing Performance‌:
      • Dual-layer silicone gaskets (Leakage rate ≤0.67m³/(m²·h) @ 1000Pa differential pressure)
      • Fire resistance rating ≥1.0 hour (GB15930-2007 Standard)
  2. Structural Design

Component Technical Specifications
Valve Body 304 SS integral stamping, 720h salt spray tested
Drive System Gear linkage mechanism, 40% faster closure
Controller DC24V electrical signal interface with fire control panel

II. Installation & Maintenance Protocols

  • Installation Requirements‌:
    • Vertically mounted at duct penetrations (tilt angle ≤15°)
    • ≥200mm clearance on actuator side for maintenance
  • Maintenance Schedule‌:

1. Quarterly: Inspect gasket compression ratio (Standard ≥30%)

2. Annually: Replace thermal sensor lubricant (High-temp silicone grease)

3. Operational Test: ≥5 manual resets during commissioning

III. Application Scenarios

Scenario Type Technical Requirements
Industrial Ventilation Chemical/O&G pipelines (316 SS mandatory)
Building Smoke Control Firewall penetrations (GB51251 fire test compliant)
Special Environments Basements/kitchens (corrosion-resistant priority)

Note‌: Smoke exhaust dampers require additional GB/T17428 cyclic wind tunnel insulation testing.

 Selected models support remote electric reset (Control voltage DC24V±10%).

Key Advantages

  1. Material Properties‌: 304/316 SS resists chloride corrosion (C1 environment rated)
  2. Smart Control‌: Real-time damper status feedback to fire control room
  3. Lifecycle‌: ≥15-year service life (with proper maintenance)
  4. This translation:

    • Uses ASHRAE/NFPA-standard terminology (e.g., "fire damper", "differential pressure")
    • Maintains original technical parameters and units
    • Follows ISO documentation conventions for tables and lists
    • Includes China-specific standards (GB) for international project compliance
    • Suitable for technical submissions, OEM manuals, and global tenders.